Step 1: Work out the head
Head is the total height the pump must push water, plus friction in the pipes, plus the pressure you want at the tap. As a rule of thumb, allow about 3 metres per floor, then add 15 to 20 metres for pipe losses and comfortable outlet pressure.
Step 2: Work out the flow
Count the outlets that can run at the same time, such as taps, showers and machines. Our team uses standard demand tables for buildings so you do not oversize. A correctly sized high head water pump saves on both purchase cost and power.
Step 3: Pick the material
Cast iron suits clean water at a lower price. For drinking water, RO and desalination, or anything warm or slightly aggressive, a stainless steel vertical pump with 316 parts lasts the longest.
Step 4: Decide on controls
A simple pressure switch is enough for small systems. For buildings and hotels, a VFD booster set with two or three vertical pumps keeps pressure steady, shares running hours between pumps and cuts energy use.
Step 5: Plan the installation
Leave space above the pump to lift the motor out for service, fit isolation valves on both sides and add a non return valve on the discharge. Our pump installation service takes care of all of this.
Quick sizing example: a ten storey building needs roughly 10 × 3 = 30 metres for height, plus about 20 metres for losses and outlet pressure. That points to a pump giving around 50 metres of head at the required flow.